Raw material and chemicals
Model No.
BioCell-B 500
BioCell-B 1000
BioCell-B 1500
BioCell-B 2000
BioCell-B 5000
Active Chlorine Generated
500 Grams/hr
1000 Grams/hr
1500 Grams/hr
2000 Grams/hr
5000 Grams/hr
Salt Consumed
2 kgs/per hour
4.5 kgs/per hour
7 kgs/per hour
9 kgs/per hour
22.5 kgs/per hour
Hypochlorite strength
7 ~ 8.0 Gpl
7 ~ 8.0 Gpl
7 ~ 8.0 Gpl
7 ~ 8.0 Gpl
7 ~ 8.0 Gpl
NaOCl Produced Per hour
70 liters
140 liters
210 liters
280 liters
700 liters
Water that can be treated with 1 ppm of chlorine(approx.)
500,000 liters per hour
1000,000 liters per hour
1500,000 liters per hour
2000,000 liters per hour
5000,000 liters per hour
AC Power Consumed
2.5kw/per hour
4.5kw/per hour
7kw/per hour
9 kw/per hour
22.5kw/per hour
Operational Considerations of Using Electrochemical Generation
NanoWater considers a few operational topics when evaluating BIOCELL-B™ plants for a facility:
Hydrogen safety
Electrical safety
Water quality, temperature and pressure
Salt quality
Electrolytic cell maintenance
BIOCELL-B™ Systems control
BIOCELL-B™ control panel should control and (or) monitor all functions and operational parameters including, but not limited to the following:
Cell safety devices such as cell temperature;
Transformer/rectifier;
DC amperage and voltage;
Hypochlorite tank levels;
Hydrogen dilution system and safety;
Hydrogen detection;
Alarm history;
Softener water and brine flow;
Conductivity of brine solution entering the electrolyzer cell;
Level of brine and storage tank;
Password control for adjustment of parameters working range of brine tank levels, product tank levels, cell voltage and amperes range and cell temperature;
Real time, brine tank level readings or indicators either on localized panel display or via HMI; and
Water pressure into the cell.
NanoWater delivers turnkey seawater electro-chlorination plant, Our projects include engineering design, manufacturing, factory assembly. Installation, testing and commissioning, our system able to meet ATEX standard – hazardous area application (Class 1 Zone 2) with stable output, our comprehensive product line is appropriate for various applications.
BIOCELL-C™ & BIOCELL-B™ are trademarks of Biotech Technologies , its subsidiaries or affiliates, in some countries. All information presented herein is believed reliable and in accordance with accepted engineering practices. Biotech Technologies makes no warranties as to the completeness of this information. Users are responsible for evaluating individual product suitability for specific applications. Biotech Technologies assumes no liability whatsoever for any special, indirect or consequential damages arising from the sale, resale or misuse of its products.